AMHS STK 사양서v2.4.2 Communication specifications for AMHS Stocker Interface · Real-time Communication and Scenarios between MCS and SCS 한국어 PDF 인쇄

Document Revision History

Date Version Modifier Comment
2026/03/27 2.4 Flowsoft Document Renewal
2026/07/08 2.4.1 Flowsoft

Content deletion due to separation of Reticle Stocker specifications

Modified VID (109~118)

Delete Port Dest Full Scenario

2026/08/10 2.4.2 Flowsoft Added functionality to the OHT / AGV port Wait out event of the transfer scenario

1 Introduction to SEMI E30 GEM

SEMI E30 GEM, also known as the Generic Equipment Model, is a communication standard designed to facilitate consistent and reliable interaction between semiconductor equipment and host software. The following section outlines its scope and the goals it aims to achieve.

1.1 Scope

The SEMI E30 GEM(GENERIC EQUIPMENT MODEL) standard focuses on defining how semiconductor equipment behaves when communicating over a link with a host system. While the SEMI E5 (SECS-II) standard defines the structure and types of messages exchanged between the host and equipment, GEM specifies which SECS-II messages to use, when to use them, and how the equipment should respond to these messages.

Importantly, GEM does not define how the host should behave; the host can initiate any communication at any time, and the equipment must react according to GEM's rules.

diagram (PDF p.4)

\

1.2 Intent

GEM establishes a standardized implementation of SECS-II specifically for semiconductor manufacturing equipment. It provides a common set of behaviors and communication features to support factory automation for device manufacturers.

The GEM standard aims to specify:

1.3 Communication State

The equipment's communication state model, as defined in SEMI E30, is divided into two main states:

When ENABLED, it includes two substates:

1.3.1 Communication State Diagram

Communication State Diagram shows how the equipment and host establish and maintain SECS-II communication.

diagram (PDF p.6)

① DISABLED

In this state SECS-II communication with a host computer is non-existent. If the operator switches from ENABLED to DISABLED, all SECS-II communications must cease immediately. Any messages queued to send shall be discarded, and all further action on any open transactions and conversations shall be terminated.

4 Handling of messages currently being transmitted is an issue for lower level message transfer protocols and is not addressed in this standard.
The DISABLED state is a possible system default.

② ENABLED / NOT COMMUNICATING

No messages other than S1,F13, S1,F14, and S9,Fx shall be sent while this substate is active. The equipment shall discard any messages received from the host other than S1,F13 or S1,F14 (Establish Communications Acknowledge). It shall also periodically attempt to establish communication with a host computer by issuing an S1,F13 until communications are successfully established. However, only one equipment-initiated S1,F13 transaction may be open at any time.

This state has two concurrent (AND-type) substates:

③ ENABLED / COMMUNICATING

⚠ Even if both sides send S1,F13 simultaneously, either successful transaction will transition the system into COMMUNICATING. The other transaction remains open until it finishes normally.

1.3.2 SECS/GEM Communication – Connection Mode Overview

In SECS/GEM communication, establishing a TCP/IP connection involves two distinct roles, determined by the connection mode configuration:

① Active Mode

② Passive Mode

1.4 Control State

1.4.1 Control State Diagram

Control State Diagram explains the equipment’s operational control modes (e.g., Offline, Online Local, Online Remote)

diagram (PDF p.8)

1.4.2 Control State: OFF-LINE

When the OFF-LINE state is active, operation of the equipment is performed by the operator at the operator console. While the equipment is OFF-LINE, message transfer is possible. However the use of messaging for any automation purpose is severely restricted. While the OFF-LINE state is active, the equipment will only respond to those messages used for the establishment of communications or a host request to activate the ON-LINE state.

While OFF-LINE, the equipment will respond with an Sx,F0 to any primary message from the host other than
S1,F13 or S1,F17.No message spooling occurs in this state. OFF-LINE consists of three substates:

① OFF-LINE / EQUIPMENT OFF-LINE

② OFF-LINE / ATTEMPT ON-LINE

③ OFF-LINE / HOST OFF-LINE

1.4.3 Control State: ON-LINE

SECS-II messages may be exchanged and acted upon. Capabilities that may be available to the host should be similar to those available from the operator console wherever practical. The use of Sx,F0 messages is not required while the ON-LINE state is active. Their use is discouraged in this case. The only allowed use is to close open transactions in conjunction with message faults.

① ON-LINE / LOCAL

② ON-LINE / REMOTE

• For equipment which supports the GEM capability of remote control (see § 4.4), while the REMOTE state is active, the host shall have access, through the communications interface, to the necessary commands to operate the equipment through the full process cycle in an automated manner. The equipment does not restrict any hostcapabilities when REMOTE is active. The degree of control executed by the host may vary from factory to factory.

• In some cases, the operator maybe required to interact during remotely controlled processes. This interaction may involve set-up operations, operator assist situations, and others. This state is intended to be flexible enough to accommodate these different situations.

To support the different factory automation policies and procedures, it shall be possible to configure the equipment to restrict the operator in specific non-emergency procedures. These restrictions shall be configurable so that the equipment may be set up to allow the operator to perform necessary functions without contention with the host. The categories for configuration shall include (but are not limited to):

No capabilities that are available to the operator when the LOCAL state is active should be unconditionally restricted when the REMOTE state is active. The supplier may provide for configurable restriction of operator capabilities not included in the list above if desired. No configurability is necessary for any operator functions not available to the host.

1.5 Reference & Verbs

No. Abbreviation Full Name Description
1 MCS Material Control System A system that manages and controls material handling equipment.
2 AMHS Automated Material Handling System Equipment used for storage and transport of materials within a factory.
3 GEM Generic Equipment Model SEMI-defined standard for generic semiconductor equipment operation.
4 Stocker-SEM Specification for AMHS Storage Specific Equipment Model SEMI standard for operating stocker-type storage systems.
5 IB-SEM Specification for Interbay / Intrabay AMHS SEM SEMI standard for operating transport equipment like AGV, OHS.
6 SC Stocker Controller Manages data and controls devices within a stocker.
7 TSC Transport System Controller Controls transport equipment such as AGVs and OHS.
8 AGV Automated Guided Vehicle Automatically delivers materials to destinations by following guide lines.
9 RGV Rail Guided Vehicle Moves along fixed rails to transport materials.
10 OHS Overhead Shuttle Ceiling-mounted shuttle that transports materials along overhead rails.
11 Lift (Vertical Transport Unit) Transfers materials between different floor levels.
12 LP Load Port Port for loading materials for processing or stocker input.
13 OP Output Port Port for dispatching materials for external transport.
14 BP Buffer Port Temporary port for intermediate or special-purpose material storage.
15 Port (General Port Interface) Generic term for LP, OP, BP – material load/unload interface points.
16 Unit (Logical/Physical Unit) General component of AMHS such as crane or shelf.
17 Crane Crane Unit Moves materials horizontally and vertically inside a stocker.

2 STK Control Specification (reference to STOCKERSEM)

This standard defines a Specific Equipment Model (SEM) for AMHS storage equipment (Stocker SEM), extending SEMI E30 requirements. It specifies the operational model and host interface (control, state models, data reports) to support integration into automated factories (e.g., semiconductor, FPD). The scope also includes queuing, carrier transfer

interface (SEMI E23), controller architecture, and scheduling/transport of transfer units.

2.1 SC State Model

The purpose of the SC state model is to provide information to the host regarding the overall status of the stocker system. The SC state model is valid when the SEMI E30 (GEM) state is ON-LINE. The SC state model is not valid when the SEMI E30 (GEM) state is OFF-LINE. Since a stocker may consist of many components (e.g.,stocker crane, conveyor, ID reader, etc.) it may be possible to continue ON-LINE operation when the operation mode of some stocker components (as viewed by the SC) is a manual state. The details of what happens when individual components of the stocker enter a manual state are specific to the Stocker SEM equipment supplier.

2.1.1 SC State Model Diagram

diagram (PDF p.12)

① SC INIT
SC initialization of stocker components is occurring. This is a non-operational state. No
commands from the host will be acknowledged, queued or processed. The system will not move out of this state if
there are carriers moving on any of the stocker units controlled by the SC. Such devices must be manually or
automatically recovered before transitioning to the next state.

② PAUSING
A system PAUSE command has been received and is being processed. All carriers that are currently moving will continue until their physical movement stops (their transfer command may still be active). Carriers that are currently moving may continue to move but they must not begin another movement. TRANSFER commands are accepted and queued. All status requests will be processed. The RESUME, INSTALL and REMOVE commands will also be processed.

③ PAUSED
No carriers are in the process of moving on any of the stocker units controlled by the SC. Carriers may be at any port position including the OP, BP, and LP positions. TRANSFER commands are accepted and queued. All status requests will be processed. The RESUME, INSTALL and REMOVE commands will also be processed.

④ AUTO
Stocker is in the normal operational state. Commands are actively processed

2.1.2 SC State Transition Table

No. Previous State Trigger New State Actions Comments
1 None SC Initiation SC Init S6F11 SCAutoInitiated
2 SC INIT System started up successfully. All Carrier movement stopped PAUSED S6F11 SCPaused
3 PAUSED RESUME command AUTO S6F11 SCAutoCompleted
4 AUTO PAUSE command PAUSING S6F11 SCPauseInitiated
5 PAUSING RESUME command AUTO S6F11 SCAutoCompleted
6 PAUSING All Carrier movement has completed PAUSED S6F11 SCPauseCompleted
7 NO ALARMS Alarm Set ALARMS S6F11 AlarmSet

S6F11

Unit Alarm Set

(in this System)

8 ALARMS All Alarms cleared NO ALARMS S6F11 AlarmCleared

S6F11

Unit Alarm Clear

(in this System)

9 ALARMS Alarm Set ALARMS S6F11 AlarmSet

S6F11

Unit Alarm Set

(in this System)

2.2 Alarm State Model

diagram (PDF p.14)

① NO ALARMS
The system is in a normal state with no active alarms.
• All equipment and operations are functioning properly.

② ALARMS (after Alarm Set)
System can process normally for transport components that are unaffected by the alarm

• The S6F11 Unit Alarm Set (AlarmSet) event is sent to the host when an alarm is raised.
• If additional alarms occur, the same message may be sent multiple times.

③ NO ALARMS (after Alarm Clear)
All previously set alarms have been cleared, and the system returns to the normal state.
• The S6F11 Unit Alarm Clear (AlarmClear) event is sent to the host upon clearing all alarms.

2.3 Transfer Command State Model

2.3.1 Transfer Command State Model Diagram

diagram (PDF p.15)

① Not Active
The transfer unit is not involved in the physical aspect of the TRANSFER command.

• This is the initial or idle state before any action is taken.

② Queued (Sub-state of Not Active)

SC has acknowledged and queued the TRANSFER command. TRANSFER command has not been initiated.

③ Active - The transfer unit is involved in the physical aspect of the TRANSFER command.

④ Transferring (Sub-state of Active)

The transfer command is actively being executed by the transport equipment.

⑤ Paused (Sub-state of Active)
The transfer command is not actively being executed by the transport equipment.

• The SC pauses execution of the TRANSFER command due to an anomaly condition..

⑥ Canceling
The TRANSFER command cancel procedure is being performed to terminate a transfer command which never entered the ACTIVE state (QUEUED). This state is entered via a CANCEL remote command.
• Host issued cancel for the TRANSFER command is accepted by the SC.

• A CANCEL remote command was issued to terminate a TRANSFER command that has not entered the physical aspect of the command.

⑦ Aborting
The TRANSFER command abort procedure is being performed to terminate a transfer command which has entered the ACTIVE state. This state can only be entered via an ABORT remote command.

• Host initiates an abort of a TRANSFER command.
• An ABORT remote command was issued to terminate a TRANSFER command.

2.3.2 Transfer Command State Transition Table

No Previous State Trigger New State Actions
1 QUEUED The TRANSFER command has been initiated by the SC. TRANSFERRING S6F11 TransferInitiated
2 QUEUED Host sends CANCEL command for a specified TRANSFER command to SC. CANCELING S6F11 TransferCancel-Initiated
3 CANCELING The cancel procedure for the TRANSFER command has completed by the stocker and the SC. None S6F11 TransferCancel-Completed
4 TRANSFERRING The SC pauses execution of the TRANSFER command due to an anomaly condition. PAUSED S6F11
TransferPaused for a specific CommandID
5 PAUSED The SC resumes execution of the TRANSFER command since the anomaly condition has been cleared. TRANSFERRING

S6F11

TransferResumed

for a specific

CommandID

6 ACTIVE

The TRANSFER command

has completed by the stocker and SC (either successfully or

unsuccessfully).

None

S6F11 TransferCompleted

sent to Host with appropriate

ResultCode

ResultCode = 0 ifsuccessful

ResultCode is nonzero if

unsuccessful

7 ACTIVE

Host sends ABORT

command for a specified

TRANSFER command to SC.

ABORTING S6F11 TransferAbort Initiated
8 ABORTING The abort procedure for the TRANSFER command has completed by the stocker and SC. None S6F11 TransferAbort Completed
9 ABORTING

TRANSFER command

cannot be aborted.

ACTIVE S6F11 TransferAbort Failed
10 CANCELING Transport system is unable to cancel the TRANSFER command because the transfer is now ACTIVE. TRANSFERRING S6F11 TransferInitiated
11 CANCELING Transport system is unable to cancel the TRANSFER command and it is still queued. QUEUED

S6F11

TransferCancel-Failed

2.4 Stocker Crane State Model

The purpose of the stocker crane state model is to provide information to the host for use of stocker crane information and metric tracking (i.e., the Host will not control the stocker crane). Whether it is possible to continue operation while the stocker crane is not operational is specific to the stocker SEM equipment supplier. If a single stocker contains multiple stocker cranes, each stocker crane must comply with the stocker crane state model.

2.4.1 Stocker Crane State Model Diagram

diagram (PDF p.17)

① IDLE
The stocker crane is not performing Host or SC initiated work.

② ACTIVE
The stocker crane is busy performing Host or SC initiated work.

③ INSERVICE
The crane is able to perform the movement of carriers. The Active and Idle states are not sub-states of this state because an Active to Idle transition can occur when the crane is ‘Out Of Service’ due to a command being canceled or aborted.

④ OUT OF SERVICE

The crane is not able to perform the movement of carriers. If a command is issued
by the Host, it shall not be rejected solely because the crane is in this state. In other words, the state of the crane is not a valid reason to reject a command from the Host.

2.4.2 Stocker Crane State Transition Table

No. Previous State Trigger New State Actions
1 IDLE Crane is requested to perform host or SC initiated work. ACTIVE S6F11 CraneActive
2 ACTIVE Crane completes host or SC initiated work. IDLE S6F11 CraneIdle
3 None System reset. OUT OF SERVICE
IN SERVICE

S6F11

UnitStateChanged

4 IN SERVICE The equipment has determined that the crane should not be used for transfers. OUT OF SERVICE

S6F11

UnitStateChanged

5 OUT OF SERVICE

The equipment has determined that the crane can be utilized for

transfers.

IN SERVICE

S6F11

UnitStateChanged

2.5 Stocker Unit State/Status Model

The stocker unit state model is intended to inform the host about unit status and metrics. It is for monitoring purposes only; the host does not control the stocker unit.

2.5.1 Unit State/Status Model Diagram

diagram (PDF p.18)

① INSERVICE
The unit is able to perform the movement or stacking/splitting of carriers.

② OUT OF SERVICE

The unit is not able to perform the movement of carriers. If a command is issued by the Host, it shall not be rejected solely because the unit is in this state. In other words, the state of the unit is not a valid reason to reject a command from the Host

③ EMPTY
The stocker unit has no carriers or wafers stored inside. It is completely empty and available to receive new items.

④ OCCUPIED(FULL) - The unit inside the stocker is occupied by a carrier, meaning it is currently full

2.5.2 Stocker Unit State/Status Transition Table

No. Previous State Trigger New State Actions
1 None System reset. OUT OF SERVICE
or IN SERVICE

S6F11

UnitStateChanged

2 IN SERVICE The equipment has determined that the stocker unit should not be used for transfers. OUT OF SERVICE

S6F11

UnitStateChanged

3 OUT OF SERVICE The equipment has determined that the stocker unit can be utilized for transfers. IN SERVICE

S6F11

UnitStateChanged

4 EMPTY The stocker unit has been occupied by any carrier. (The location is Full)

OCCUPIED

(FULL)

S6F11

UnitStatusChanged

5

OCCUPIED

(FULL)

The stocker unit does not have any carrier. (The location is Empty) EMPTY

S6F11

UnitStatusChanged

2.6 Carrier State Model

The purpose of the stocker carrier state model is to provide information to the host regarding carrier tracking (the Host will not control carriers) while the carrier is in the domain of the stocker. The carrier is in the domain of the stocker when it is in storage or transport internal to the stocker or on a stocker interface port (manual, interbay, or intrabay). The equipment shall track each carrier in compliance with the Stocker Carrier State Model.

2.6.1 Carrier State Model Diagram

diagram (PDF p.20)

① INSTALLED - Carrier in stocker database.
② WAIT IN (INSTALLED sub-state)

Carrier at final internal port location of the stocker. Carrier is ready to be transferred to storage or output location and no further movement or action should be taken on this carrier prior to transfer.

③ WAIT OUT (INSTALLED sub-state) - Carrier is at an Output, Buffer, or Loading Port.
④ TRANSFERRING (INSTALLED sub-state)

Carrier ‘moving’ between locations in the stocker. The carrier may not be physically moving but may be on the crane (or other position) waiting for a new TRANSFER command as the result of an anomaly condition.

⑤ STORED (INSTALLED sub-state) - Carrier is sitting at a storage location.
⑥ COMPLETED (STORED sub-state)

The carrier is stored at a shelf location as a result of completing a transfer for which this shelf represents the destination of the transfer command.

⑦ ALTERNATE (STORED sub-state)

The carrier is temporarily stored at a shelf location. The transfer command completion is pending until the destination and the crane become available.

2.6.2 Carrier State Transition Table

No. Previous State Trigger New State Actions
1 None Carrier arrives at a Wait In position of the stocker. WAIT IN

S6F11

CarrierWaitIn

2 WAIT IN

Stocker is executing a

TRANSFER command

for the carrier.

TRANSFERRING

S6F11

CarrierTransferring

3 TRANSFERRING Completion of a TRANSFER command with a DEST of internal stocker storage. COMPLETED

S6F11

CarrierStored

4 COMPLETED

Stocker is executing a

TRANSFER command

for the carrier.

TRANSFERRING

S6F11

CarrierTransferring

5 TRANSFERRING

Carrier has arrived at

the output port.

WAIT OUT

S6F11

CarrierWaitOut

6 WAIT OUT

Carrier has advanced

(automatically) on a

port beyond the output

port.

WAIT OUT

S6F11

CarrierWaitOut

7 WAIT OUT

Carrier is removed from

the stocker domain (removed from the output LP).

None

S6F11

CarrierRemoved

8 TRANSFERRING

The destination of the

move command is occupied.

ALTERNATE

S6F11

CarrierStoredAlt

9 ALTERNATE

The port becomes available and transfer command is first in

queue.

TRANSFERRING

S6F11

TransferResumed

10 None

Carrier entry is created

or modified in the SC

database.

COMPLETED

S6F11

CarrierInstallCompleted

11 INSTALLED

Carrier entry is removed

from the SC database.

None

S6F11

CarrierRemoveCompleted

12 ALTERNATE Transfer Command is Aborted COMPLETED

S6F11

CarrierStored

13 WAIT OUT Carrier on a bi-directional port is ready to be moved to a storage or output location. WAIT IN

S6F11

Carrier Wait In

14 None The result of ID read at an output port that did not match the expected ID. WAIT OUT

S6F11

Carrier Wait Out

15 None

1.Carrier created directly on the crane(as the result of duplicate ID recovery).

2.Transfer Command received from host with the source being a port with no SC controlled sensors (e.g.directly connected process equipment)

TRANSFERRING

S6F11

CarrierTransferring

16 TRANSFERRING

Carrier has arrived at an

Output port and is removed from the stocker domain.

None

S6F11

CarrierRemoved

2.7 ID RULE

2.7.1 Command ID

(H/U/C) + Carrier ID + Time(yyyyMMddHHmmssfff)

System Prefix Example
MES, MCS SERVER H H+CARRIER01+20160904093931123
MCS UI U U+CARRIER01+20160904093931123
STOCKER C C+CARRIER01+20160904093931123

2.7.2 Carrier ID

Case Format
Example

ID Read Fail

(Prefix UNK)

UNK_UnitID_DateTime(yyyyMMddHHmmssfff)
Ex) UNK_STK-K54-BM-02_LP01_20160908093931123

Duplicate

(Prefix DUP)

DUP_CarrierID_DateTime(yyyyMMddHHmmssfff)
Ex) DUP_CST001_20160908093931123

DoubleStore

(Prefix DBS)

DBS_UnitID_DateTime(yyyyMMddHHmmssfff)
Ex) DBS_STK-K54-BM-02_20403_20180622165955230

2.7.3 Machine/Unit ID

Item Format
Example
STOCKERID TscType-{Factory + Floor}-{Process Group}-{Stocker No}
Ex) STK-K52-BM-01, STK-K52-BM-02, STK-K54-BM-01, STK-K54-BM-02
UNITID

Access Mode AUTO Type

Input : {STOCKERID}_LP01

Output: {STOCKERID}_OP01

Ex) STK-K54-BM-01_LP01 , STK-K54-BM-01_OP01

Access Mode Not AUTO Type(*Manual Port is recommended to be 6 (six) or higher)

Input : {STOCKERID}_LP06

Output : {STOCKERID}_OP06

Ex) STK-K54-BM-03_LP06, STK-K54-BM-01_OP06
SHELFID {STOCKERID}_{zxxyy}
- Format: ZXXYY (5 Digit, Bank/Bay/Level)
Ex) STK-K54-BM-01_10101 ~ STK-K54-BM-01_2xxyy
CRANEID {STOCKERID}_RM01
Ex) STK-K54-BM-01_RM01

3 SECS Messages Specification(SECS-II)

SECS-II, short for SEMI Equipment Communications Standard – Low-Level protocol, defines the low-level rules and procedures for transmitting messages between a semiconductor equipment (tool) and a host computer (usually MES or CIM systems).

It is essentially the transport layer that ensures reliable delivery of SECS-II messages.

3.1 Stream Function Definitions

3.1.1 Stream1

Messages Direction Description
SxF0 H<->E Abort Transaction
S1F1 H<->E Are You There Request (R)
S1F2 H<->E On-line Data (D)
S1F3 H -> E Selected Equipment Status Request (SSR)
S1F4 H <- E Selected Equipment Status Data (SSD)
S1F13 H<->E Establish Communication Request (CR)
S1F14 H<->E Establish Communication Request Ack. (CRA)
S1F15 H -> E Request OFF-LINE(ROFL)
S1F16 H <- E OFF-LINE Ack. (OFLA)
S1F17 H -> E Request ON-LINE(RONL)
S1F18 H <- E ON-LINE Ack. (ONLA)

3.1.2 Stream2

Messages Direction Description
S2F31 H -> E Date and Time Set Request (DTS)
S2F32 H <- E Date and Time Set Ack. (DTA)
S2F41 H -> E Host Command Send (HCS)
S2F42 H <- E Host Command Ack. (HCA)
S2F49 H -> E Enhanced Remote Command
S2F50 H <- E Enhanced Remote Command Ack.

3.1.3 Stream3

Messages Direction Description
S3F101 H -> E Lot Information

3.1.4 Stream5

Messages Direction Description
S5F1 H <- E Alarm Report send (ARS)
S5F2 H -> E Alarm Report Acknowledge (ARA)
S5F3 H -> E Alarm Valid/Invalid Setting
S5F4 H <- E Alarm Valid/Invalid Setting Acknowledge
S5F5 H -> E Alarm List Request
S5F6 H <- E Alarm List Request Acknowledge

3.1.5 Stream6

Messages Direction Description
S6F11 H <- E Event Report Send(ERS)
S6F12 H -> E Event Report Acknowledge(ERA)

3.1.6 Stream9

Messages Direction Description
S9F1 H <- E Unrecognized Device ID
S9F3 H <- E Unrecognized Stream Type
S9F5 H <- E Unrecognized Function Type
S9F7 H <- E Illegal Data
S9F9 H <- E Transaction Timer Timeout

3.1.7 Stream10

Messages Direction Description
S10F3 H -> E Terminal Display
S10F4 H <- E Terminal Display Ack.

3.2 Event Report Definition

3.2.1 Controller State Event

CEID NAME STATE
OLD NEW
1101 OFFLINE LOCAL, REMOTE OFFLINE
1102 LOCAL OFFLINE, REMOTE LOCAL
1103 REMOTE OFFLINE, LOCAL REMOTE

3.2.2 SC State Transition Event

CEID NAME STATE
OLD NEW
1201 SC Auto Initiated None SC Init
1202 SC Auto Complete Paused, Pausing Auto
1203 SC Pause Initiated Auto Pausing
1204 SC Pause Completed Pausing Paused
1205 SC Paused SC Init Paused

3.2.3 Transfer Command Transition Event

CEID NAME STATE
OLD NEW
3101 Transfer Initiated QUEUED TRANSFERRING
3102 Transfer Completed ACTIVE NONE
3103 Transfer Paused TRANSFERRING PAUSED
3104 Transfer Resumed PAUSED TRANSFERRING
3201 Transfer Abort Initiated ACTIVE ABORTING
3202 Transfer Abort Completed ABORTING NONE
3203 Transfer Abort Failed ABORTING ACTIVE
3301 Transfer Cancel Initiated QUEUED CANCELING
3302 Transfer Cancel Completed CANCELING NONE
3303 Transfer Cancel Failed CANCELING QUEUED

3.2.4 Crane State Transition Event

CEID NAME STATE
OLD NEW
4101 Crane Active IDLE ACTIVE
4102 Crane Idle ACTIVE IDLE

3.2.5 Alarm State Transition Event

CEID NAME STATE
OLD NEW
1303 Unit Alarm Set

NONE

ALARM

ALARM
1304 Unit Alarm Clear ALARM NONE

3.2.6 Carrier State Transition Event

CEID NAME STATE
OLD NEW
2101 Carrier ID read
2102 Carrier wait in NONE WAITIN
2103 Carrier transferring WAITIN TRANSFERRING
2104 Carrier stored TRANSFERRING COMPLETED
2105 Carrier stored alt TRANSFERRING ALTERNATE
2106 Carrier wait out TRANSFERRING WAITOUT
2107 Carrier removed WAITOUT NONE
2201 Carrier install complete NONE INSTALL(COMPLETED)
2202 Carrier remove complete INSTALL NONE

3.2.7 Operator Event

CEID NAME STATE
OLD NEW
4301 Operator Init Action NONE NONE

3.2.8 Zone Status Transition Event

CEID NAME STATE
OLD NEW
4201 Zone Capacity Change NONE NONE

3.2.9 State Event

CEID NAME STATE
OLD NEW
5101 Unit State Changed

Inservice

Out of Service

Out of Service

Inservice

5102 Unit Status Changed

Empty

Occupied

Occupied

Empty

3.3 Variable Data Items

3.3.1 Basic VID

VID Name Class Format Details
1 SC Name SV/DV A,64

SC ID

Eqp Name

2 Control State SV/DV U2,1

1: Eqp Offline

2: Attempt Online

3: Host Offline

4: Online Local

5: Online Remote

3 SC State SV/DV U2,1

1=SC Init

2=Paused

3=Auto

4=Pausing

4 Active Carriers SV

L,n

<CarrierInfo>

5 Active Transfers SV

L,n

<TransferCommand>

6 Active Zones SV

L,n

<ZoneData>

7 All Unit Infos SV

L,n

<Unit Info>

VID 16
8 All Shelf Infos SV

L,n

<Shelf Info>

VID 17
9 Active Alarms SV

L,n

<AlarmInfo>

VID=18
10 Active Unit Alarms SV

L,n

<UnitAlarmInfo>

VID=19
VID Name Class Format Details
11 CarrierInfo SV/DV

L,2

<A,64 CarrierID>

<A,64 CarrierLoc>

12 TransferCommand SV/DV

L,2

<CommandInfo>

<TransferInfo>

13 CommandInfo SV/DV

L,2

<A,64 CommandID>

<U2,1 Priority>

Priority 1~99
14 TransferInfo SV/DV

L,4

<A,64 CarrierID>

<A,64 CarrierLoc>

<A,64 Source>

<A,64 Dest>

15 ZoneData SV/DV

L,3

<A,64 Zone Name>

<U2,1 Zone Capacity>

<U2,1 Max Capacity>

16 UnitInfo SV/DV

L,3

<A,64 Unit ID>

<U2,1 Unit State>

<U2,1 Unit Status>

Port or Crane(RM)
17 Shelf Info SV

L,4

<A,64 Shelf Unit ID>

<A,64 Zone Name>

<U2,1 Shelf Unit State>

<A,64 Carrier ID>

18 Alarm Info SV

L3

<B,1 Alarm code>

<U2,1 Alarm ID>

<A, 128 Alarm Text>

19 Unit Alarm Info SV/DV

L3

<A,64 UnitID>

<U2,1 Alarm ID>

<A, 128 Alarm Text>

3.3.2 Transfer & Device VID

VID Name Class Format Details
101 CommandID DV A,64
102 CarrierID DV A,64
103 UnitID DV A,64 Crane, Port, Shelf
104 ErrorID DV A,64
105 Unit State SV/DV U2

Unit: Port, Crane, Shelf

1: Out of Service

2: Inservice

106 Unit Status SV/DV U2

Unit: Port, Crane, Shelf

1: Empty

2: Occupied(Full)

107 Transfer State DV U2,1

Transfer State

1: Queued

2: Transferring

3: Paused

4: Canceling

5: Aborting

108 Carrier State DV U2,1

Carrier State

0: None

1: Wait In

2: Transferring

3: Completed

4: Alternate

5: Wait Out

109 ZoneName DV A,64
110 ZoneCapacity DV U2 Available Capacity
111 MaxCapacity SV U2 Total Capacity
112 SubCarrierID SV A,64
113 EmptyCarrierCount SV/DV U2
114 Source DV A,64
115 Dest DV A,64
116 CarrierLoc DV A, 64
117 AlarmID SV U2
118 AlarmText SV/DV A,128

3.3.3 Option & Error Code

VID Name Class Format Details
201 Recovery Option DV A,64

blank

RETRY

ABORT

202 Result code DV U2,1

Transfer Complete Item

0: Success

1: Other Error

2: Shelf zone is full

3: Duplicate ID

4: Mismatch ID

5: Failure to Read ID

203 PortType DV A,20

LP, BP, OP

LP: Loading port

BP: Buffer port

OP: Output port

204 CommandType DV A,20

Transfer type used for operator-initiated actions.

-TRANSFER

-CANCEL

-ABORT

205 Failure Code DV U2,1

S6F11 item corresponding to RCMD

1: Undefined Failure

2: Location Occupied(Install Rcmd)

3: Carrier Not Exist

(Remove Rcmd)

206 HandoffType DV U2,1

1: Manual

2: Automated

207 IDRead Status DV U2,1

0: OK

1: Fail

2: Duplicate

3: Mismatch

208 IDRead Duplicate-option SV/ECV/DV U2,1

0: Reject

1: Host control

209 IDRead Failure-option SV/ECV/DV U2,1

0: Reject

1: Host control

210 IDRead Mismatch-option SV/ECV/DV U2,1

0: Reject

1: Host control

3.4 Remote Command Definitions

3.4.1 Remote Command Name(S2F41, F49)

RCMD CPNAME REQ/OPT COMMENT
ABORT “COMMANDID” R Requests termination of a specific active transfer command identified by COMMANDID. Execution depends on the equipment's current state.
CANCEL “COMMANDID” R Requests cancellation of a specific queued transfer command identified by COMMANDID. Can be executed regardless of the equipment's state.
PAUSE NONE N/A Requests the equipment to switch to Pause mode
RESUME NONE N/A

Requests the equipment to switch back

to Auto mode from Pause.

TRANSFER

“COMMANDINFO”

“TRANSFERINFO”

R Typically used instead of S2F41; requests the transfer of a carrier from a specific source to a designated destination.
REMOVE “CARRIERID” R Delete the corresponding carrier information from the SC database.
INSTALL

“CARRIERID”

“CARRIERLOC”

“LOTID”

R Insert specific carrier information into the SC database.

3.4.2 Remote Command Parameters

CPNAME Format COMMENT
COMMANDID A[64] Unique identifier of commands generated by the MCS
PRIORITY U2[1]

Execution priority of Remote Command

Low 1 ~ 99 High

CARRIERID A[64] Unique Carrier Id
CARRIERLOC A[64] Unique Carrier Location Within The Stocker
LOTID A[64] Lot Number
SOURCE A[64] Unique Source Location
DEST A[64] Destination Location
CPNAME GROUP COMMENT
COMMANDINFO

<L2

<COMMANDID

<PRIORITY

TRANSFERINFO

<L3

<CARRIERID

<SOURCE

<DEST

3.5 Stream Function Details

RPTID Reserved (Deprecated)

RPTID Status Note
2 Reserved Deprecated. Reserved for backward compatibility — not to be reused.
3 Reserved Deprecated. Reserved for backward compatibility — not to be reused.

3.5.1 S1F1-Are you there

Stream Function Description Wait bit Direction
1 1 Establish if the equipment is on line True H<->E
HEADER ONLY.
Stream Function Description Wait bit Direction
1 2 Data signifying that the equipment is alive False H<-E

< L, 2

< A[64] MDLN> * Model Number of the equipment

< A[64] SOFTREV> * Software Revision

Stream Function Description Wait bit Direction
1 2 Data signifying that the host is alive False H->E
< L, 0

3.5.2 S1F3-Selected Equipment Status Request

Stream Function Description Wait bit Direction
1 3 HOST QUERY AMHS EQ INFO True H->E

<L,8

<U2,1 2> /*control state */

<U2,1 3> /*SC state */

<U2,1 4> /Active Carriers

<U2,1 5> /Active Transfers

<U2,1 6> /Active Zones

<U2,1 7> /All Unit info

<U2,1 8> /All Shelf info

<U2,1 10> / Active Unit Alarms

Stream Function Description Wait bit Direction
1 4 False H<-E

<L,8

<U2,1 Control state

<U2,1 SC state

<L n Carrier info

<L 2

<A,64 CarrierID

<A,64 Carrier Loc

<L,n Transfer Info

<L,2

<L,2 Command info

<A,64 CommandID

<U2,1 Priority

<L,4 Carrier Info

<A,64 CarrierID

<A,64 CarrierLoc

<A,64 Source

<A,64 Dest

<L,n Zone info

<L,3

<A,64 Zone Name

<U2,1 Zone Capacity

<U2,1 Zone MaxCapacity

<L,n Unit info

<L,3

<A,64 Unit ID

<U2,1 Unit state

<U2,1 Unit status

<L,n Shelf info

<L,4

<A,64 Shelf ID

<A,64 Zone Name

<U2,1 Shelf Unit State

<A,64 Carrier ID

<L,n Active Unit Alarms

<L,3

<A,64 Unit ID

<U2,1 Alarm ID

<A,128 Alarm text

3.5.3 S1F13-Establish Communication Request

Stream Function Description Wait bit Direction
1 13

Initialize communications at a logical application

level both on power-up and following a break in

communications.

True H<->E

E->H

<L 2

<A[64] MDLN>

<A[64] SOFTREV>

H->E

<L 0

Stream Function Description Wait bit Direction
1 14 Accept or deny Establish Communication Request False H<->E

E->H

<L, 2

<B[1] COMMACK>

<L, 2

<A[64] MDLN>

<A[64] SOFTREV>

H->E

<L, 2

<B[1] COMMACK>

<L 0

3.5.4 S1F15-Offline Request

Stream Function Description Wait bit Direction
1 15

The Host requests that the equipment transaction

to the OFF-LINE state.

True H->E
Header Only
Stream Function Description Wait bit Direction
1 16 Acknowledge or Error. False H<-E
<B[1] OFLACK

3.5.5 S1F17-Online Request

Stream Function Description Wait bit Direction
1 17

The Host requests that the equipment transaction

to the ON-LINE state.

True H->E
Stream Function Description Wait bit Direction
1 18 Acknowledge or Error. False H<-E

<B[1] ONLACK

0: OK

1: Not-Allowed

2: Already online

3.5.6 S2F31-Date and Time Request

Stream Function Description Wait bit Direction
2 31

Useful to synchronize the equipment time with the

host time base.

True H->E
<A[16] TIME
Stream Function Description Wait bit Direction
2 32 Acknowledge the receipt of time and date. False H<-E
<B[1] TIACK

3.5.7 S2F41-Host Command Send(Remove)

Stream Function Description Wait bit Direction
2 41 SC DB Delete by carrier id True H->E

< L, 2

< A[64] RCMD > * REMOVE

< L ,1

<L, 2

<A,64 CPNAME > * CARRIERID

<A,64 CPVAL > * CarrierID

3.5.8 S2F41-Host Command Send(Install)

Stream Function Description Wait bit Direction
2 41 SC DB Update By Carrier Id True H->E

< L, 2

< A[64] RCMD > * 'INSTALL'

< L, 3

<L, 2

<A,64 CPNAME > * 'CARRIERID'

<A,64 CPVAL > * CarrierID

<L, 2

<A,64 CPNAME > * ‘CARRIERLOC'

<A,64 CPVAL > * Carrier Current Location

<L, 2

<A,64 CPNAME > * ‘LOTID'

<A,64 CPVAL > * LOTID value

3.5.9 S2F41-Host Command Send(Cancel)

Stream Function Description Wait bit Direction
2 41

The Host Requests the Equipment perform the

specified remote command with the associated parameters.

True H->E

< L, 2

< A[64] RCMD > * CANCEL

< L ,1

<L, 2

<A,64 CPNAME > * COMMANDID

<A,64 CPVAL > * CommandId

3.5.10 S2F41-Host Command Send(Abort)

Stream Function Description Wait bit Direction
2 41

The Host Requests the Equipment perform the

specified remote command with the associated parameters.

True H->E

< L, 2

< A[64] RCMD > * ABORT

< L, 1

<L, 2

<A[64] CPNAME > * COMMANDID

<A[64] CPVAL > * CommandId

3.5.11 S2F41-Host Command Send(Pause)

Stream Function Description Wait bit Direction
2 41

The Host Requests the Equipment perform the

specified remote command with the associated parameters.

True H->E

< L, 2

< A[64] RCMD > * PAUSE

< L, 0

3.5.12 S2F41-Host Command Send (Resume)

Stream Function Description Wait bit Direction
2 41

The Host Requests the Equipment perform the

specified remote command with the associated parameters.

True H->E

< L, 2

< A[64] RCMD > * RESUME

< L, 0

3.5.13 S2F42-Host Command Acknowledge

Stream Function Description Wait bit Direction
2 42

Acknowledge Host command or error. If command

is not accepted due to one or more invalid

parameters.

False H<-E

No Error

< L, 2

< B[1] HCACK > 0

< L ,0

Some Error

< L, 2

< B[1] HCACK > 3

< L ,2

<L, 2

<A,64 CPNAME > Command Parameter Name

<B[1] CPVAL > Control Parameter Ack Code

.................

<L, 2

<A,64 CPNAME > Command Parameter Name

<B[1] CPVAL > Control Parameter Ack Code

  • Request HCACK= 5 for the same command

  • 0 : Acknowledge, command has been performed

  • 1 : Command does not exist

  • 2 : Cannot perform now

  • 3 : At least one parameter is invalid

  • 4 : Acknowledge, command will be performed with completion signaled later by an event

  • 5 : Rejected, Already in Desired Condition

  • 6 : No such object exist

  • 7 – 63 : Reserved

3.5.14 S2F49-Transfer

Stream Function Description Wait bit Direction
2 49 The Host requests the equipment perform the specified enhanced remote command (TRANSFER) with the associated parameters True H->E

< L, 4

< U2 DATAID>

< A[64] OBJSPEC>

< A[64] RCMD> * TRANSFER

< L 2

<L, 2

<A,64 CPNAME > * COMMANDINFO'

<L, 2

<L, 2

<A,64 CPNAME > * COMMANDID''

<A,64 CPVAL > * CommandID

<L, 2

<A,64 CPNAME > * PRIORITY'

<U2[1] CPVAL > * Priority

<L, 2

<A,64 CPNAME > * TRANSFERINFO

<L, 3

<L, 2

<A,64 CPNAME > * 'CARRIERID'

<A,64 CPVAL > * CarrierID

<L, 2

<A,64 CPNAME > * 'SOURCE' * ZONENAME, PORTID

<A,64 CPVAL > * Source

<L, 2

<A,64 CPNAME > * 'DEST' * ZONENAME, PORTID

<A,64 CPVAL > * Destination

3.5.15 S2F50-Enhanced Remote Command Acknowledge

Stream Function Description Wait bit Direction
2 50

The equipment acknowledge Enhanced Remote Command or

reports any error(s). If the command is not accepted due to

one or more invalid parameters, (i.e. HCACK=3), then a list

of invalid parameters will be returned containing the

parameter name and reason for being invalid.

False H<-E

No Error

< L, 2

< B[1] HCACK > 0

< L ,0

Some Error

< L, 2

< B[1] HCACK > 3

< L ,2

<L, 2

<A,64 CPNAME > Command Parameter Name

<B[1] CPEACK > Control Parameter Ack Code

.................

<L, 2

<A,64 CPNAME > Command Parameter Name

<B[1] CPEACK > Control Parameter Ack Code

  • Request HCACK= 5 for the same command

  • 0 : Acknowledge, command has been performed

  • 1 : Command does not exist

  • 2 : Cannot perform now

  • 3 : At least one parameter is invalid

  • 4 : Acknowledge, command will be performed with completion signaled later by an event

  • 5 : Rejected, Already in Desired Condition

  • 6 : No such object exist

  • 7 – 63 : Reserved

3.5.16 S3F101-LOT INFO SEND

Stream Function Description Wait bit Direction
3 101 Lot Info Send True H->E

<L, 10

<L, 2

<A,64 $VNAME > * CUSTOMER

<A,64 $VVAL > * Customer value

<L, 2

<A,64 $VNAME > * STRIPMARKING

<A,64 $VVAL > * Strip marking

<L, 2

<A,64 $VNAME > * LOTNUMBER

<A,64 $VVAL > * Lot Number value

<L, 2

<A,64 $VNAME > * CARRIERID

<A,64 $VVAL > * CarrierID

<L, 2

<A,64 $VNAME > * LOTID

<A,64 $VVAL > * LOTID

<L, 2

<A,64 $VNAME > * SUBID

<A,64 $VVAL > * SUBID Value

<L, 2

<A,64 $VNAME > * LOTTYPE

<A,64 $VVAL > * LOTTYPE Value

<L, 2

<A,64 $VNAME > * DCC

<A,64 $VVAL > * DCC Value

<L, 2

<A,64 $VNAME > * OP

<A,64 $VVAL > * OP Value

<L, 2

<A,64 $VNAME > * CustName

<A,64 $VVAL > * CustName Value

Stream Function Description Wait bit Direction
3 102 Lot Info Send Ack False H<-E
< B [1] LIACK>

3.5.17 S5F1-Alarm Report

Stream Function Description Wait bit Direction
5 1

This message reports a change in or presence of

an alarm condition.

True H<-E

< L, 3

< B [1] ALCD> * Alarm Code

< U2 [1] ALID> * Alarm Id

< A[128] ALTX> * Alarm Text

Stream Function Description Wait bit Direction
5 2 Acknowledge or error. False H->E
< B [1] ACKC5>

3.5.18 S5F3-Alarm Valid/Invalid Setting

Stream Function Description Wait bit Direction
5 3 Valid/Invalid Alarms True H->E

< L, 2

< B [1] ALED> * Alarm Valid/Invalid Code

< U2 [1] ALID> * Alarm Id

Stream Function Description Wait bit Direction
5 4 Acknowledge to Alarm Valid/Invalid Setting False H<-E
< B [1] ACKC5>

3.5.19 S5F5-Alarm List

Stream Function Description Wait bit Direction
5 5 Alarm List Request True H->E

< L, n

< U2 [1] ALID> * Requested Alarm Id

..................

< U2 [1] ALID> * Requested Alarm Id

Or

<L, 0 : All Alarm Request

Stream Function Description Wait bit Direction
5 6 Acknowledge to Alarm List Request False H<-E

<L, n

< L, 3

< B [1] ALCD> * Alarm Code

< U2 [1] ALID> * Alarm Id

< A[128] ALTX> * Alarm Text

...................

< L, 3

< B [1] ALCD> * Alarm Code

< U2 [1] ALID> * Alarm Id

< A[128] ALTX> * Alarm Text

3.5.20 S6F11-Event Report Send (RPTID 1)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 3

<A,64 EqpName>

<U2,1 Control state>

<U2,1 SC state>

CEID Event Name
1101 OFFLINE
1102 LOCAL
1103 REMOTE
1201 Auto Init
1202 Auto Complete
1203 Pause Init
1204 Pause Complete
1205 Paused

3.5.21 S6F11-Event Report Send (RPTID 4)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 2

<L,2

<A,64 CarrierID>

<A,64 Carrier Loc>

<U2[1] IDReadStatus>

CEID Event Name
2101 Carrier ID Read

3.5.22 S6F11-Event Report Send (RPTID 5)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 1

<L,2

<A,64 CarrierID>

<A,64 Carrier Loc>

CEID Event Name
2102 Carrier Wait in
2103 Carrier Transferring
2104 Carrier Stored
2105 Carrier Stored Alt
2106 Carrier Wait Out
2201 Carrier Install Complete
2202 Carrier Remove Complete

3.5.23 S6F11-Event Report Send (RPTID 6)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 2

<L,2

<A,64 CarrierID>

<A,64 Carrier Loc>

<U2[1] HandoffType>

CEID Event Name
2107 Carrier removed

3.5.24 S6F11-Event Report Send (RPTID 7)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 2

<L,2

<A,64 CommandID>

<U2,1 Priority>

<L,4

<A,64 CarrierID>

<A,64 CarrierLoc>

<A,64 Source>

<A,64 Dest>

CEID Event Name
3101 Transfer Initiated
3103 Transfer Paused
3104 Transfer Resumed
3201 Transfer Abort Initiated
3202 Transfer Abort Completed
3203 Transfer Abort Failed
3301 Transfer Cancel Initiated
3302 Transfer Cancel Completed
3303 Transfer Cancel Failed

3.5.25 S6F11-Event Report Send (RPTID 8)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L,3

<L,2

<A,64 CommandID>

<U2,1 Priority>

<L,4

<A,64 CarrierID>

<A,64 CarrierLoc>

<A,64 Source>

<A,64 Dest>

<U2,1 ResultCode>

CEID Event Name
3102 Transfer complete

3.5.26 S6F11-Event Report Send (RPTID 9)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L,3

<L,2

<A,64 CommandID>

<U2,1 Priority>

<L,4

<A,64 CarrierID>

<A,64 CarrierLoc>

<A,64 Source>

<A,64 Dest>

<A,20 CommandType

CEID Event Name
4301 Operator init action

3.5.27 S6F11-Event Report Send (RPTID 10)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L 2

<L2

<A,64 CommandID>

<U2,1 Priority>

<A,64 UnitID> CraneID

CEID Event Name
4101 ACTIVE
4102 IDLE

3.5.28 S6F11-Event Report Send (RPTID 11)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 2

<A,64 UnitID> CraneID, PortID, ShelfID

<U2[1] Unit State>

CEID Event Name
5101 Unit State Changed (1: Out of Service, 2: Inservice)

3.5.29 S6F11-Event Report Send (RPTID 12)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 2

<A,64 UnitID> CraneID, PortID, ShelfID

<U2[1] Unit Status>

CEID Event Name
5102 Unit status changed (1: Empty, 2: Occupied)

3.5.30 S6F11-Event Report Send (RPTID 13)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L,1

<L, 3

<A,64 Zone Name>

<U2,1 Zone Capacity>

<U2,1 Max Capacity>

CEID Event Name
4201 Zone Capacity Change

3.5.31 S6F11- Event Report Send (RPTID 14)

Stream Function Description Wait bit Direction
6 11 The equipment send event True H<-E

< L, 3

< U2 [1] DATAID>

< U2 [1] CEID>

<L, 1

< L, 2

<U2 [1] RPTID>

<L, 1

<L, 3

<A,64 Unit ID>

<U2,1 AlarmID>

<A,128 AlarmText>

CEID Event Name
1303 Unit Alarm Set
1304 Unit Alarm Clear

3.5.32 S6F12-Event Report Acknowledge

Stream Function Description Wait bit Direction
6 12 Acknowledge or error. False H->E
<B1 ACKC6>.

3.5.33 S9F1/3/5/7/9-Transaction Error

Stream Function Description Wait bit Direction
9 1 Unrecognized Device ID True H<-E
< MHEAD B[10]>
Stream Function Description Wait bit Direction
9 3 Unrecognized Stream Type True H<-E
< MHEAD B[10]>
Stream Function Description Wait bit Direction
9 5 Unrecognized Function Type True H<-E
< MHEAD B[10]>
Stream Function Description Wait bit Direction
9 7 Illegal Data True H<-E
< MHEAD B[10]>
Stream Function Description Wait bit Direction
9 9 Transaction Timer Timeout True H<-E
< SHEAD B[10]>

3.5.34 S10F3-Terminal Display (Single)

Stream Function Description Wait bit Direction
10 3 Terminal Display, Single True H->E

< L, 2

< B [1] TID> * Terminal Id

< A[1024] TEXT> * Terminal Text

Stream Function Description Wait bit Direction
10 4 Acknowledge or error. False H<-E
< B [1] ACKC10>

4 Scenario

4.1 Initialize

4.1.1 Initialize On Connect

diagram (PDF p.63)

4.1.2 Initialize By SC Offline -> Remote

diagram (PDF p.64)

4.2 Mode Change

4.2.1 On-Line -> Off-Line(By SC)

diagram (PDF p.65)

4.2.2 On-Line -> Off-Line(By MCS)

diagram (PDF p.65)

4.2.3 SC Unit Event

diagram (PDF p.66)

4.3 Scenario

4.3.1 Transfer Operation

4.3.1.1 Normal Scenario(Input => Shelf)

diagram (PDF p.67)

4.3.1.2 Normal Scenario (Shelf => Output)

diagram (PDF p.68)

4.3.1.3 Normal Scenario(Input => Output)

diagram (PDF p.69)

4.3.1.4 Normal Scenario(Shelf => Shelf)

diagram (PDF p.70)

4.3.2 Data Management

4.3.2.1 Install Command

diagram (PDF p.71)

4.3.2.2 Remove Command

diagram (PDF p.71)

4.3.3 Remote Command

4.3.3.1 Cancel

diagram (PDF p.72)

4.3.3.2 Abort

diagram (PDF p.72)

4.3.3.3 SC Pause/Resume

diagram (PDF p.73)

4.4 Abnormal Process

4.4.1 Host Timeout

diagram (PDF p.74)

4.4.2 Source Empty

diagram (PDF p.75)

4.4.3 Shelf Destination Full(Double Store)

diagram (PDF p.76)

4.4.4 Output Port is not Available

diagram (PDF p.77)

4.4.5 RFID Reading Error(Source Input Port)

diagram (PDF p.78)

4.4.6 RFID Duplicate Error(Input Port)

diagram (PDF p.79)

4.5 Alarm

4.5.1 Alarm Set/Clear

diagram (PDF p.81)

4.6 Operator Scenario

4.6.1 Operator(Command Type-Cancel, Abort)-SC Manual Cancel

diagram (PDF p.82)

4.6.2 Operator(Command Type-Transfer)-SC Manual Transfer

diagram (PDF p.83)